Cramer Residence — Mechanical
1217 TWIN CREEK RD, APEX NC · MANUAL J REV D
M1.1Sheet
Loading M1.1…
Trunk Branch Register Air handler
Loading M1.2…
Trunk Branch Register Air handler

Equipment Schedule

Sizing note. Calculated total is 5.07 tons. Specifying 2.5 + 1.5 + 1.5 + 1.0 gives 6.5 nominal — about 28% over. Each unit must cover its own zone peak alone, and items marked * are already at the smallest capacity commonly available in a split heat pump. Zones 3 and 4 calculate below 1 ton, so ducted mini-splits are the closer match and would bring the total to roughly 6.0.

Orientation. Facade faces southwest, so plan-up is SW and the rear patio wall faces NE. Glazing splits . Because the largest wall of glass faces northeast it takes almost no afternoon sun — that is why the calculated load fell from 5.46 to 5.07 tons once true orientation replaced the earlier southwest assumption.

Room Schedule

Design airflow, outlet count and branch size per room. Colour bar at left marks the serving air handler.

ZoneRoomAreaHeatCoolCFMOutØ